| Model | | | SM-960 |
|
| Dimensions | | | 96(W) × 96(H) × 100(D) |
|
| Panel size | | | 92(W) × 92(H) |
|
| Power Supply | | | AC100~240V(permissible power range ± 10%) 50/60 ㎐ |
|
| Power Consumption | | | 6.0W, MAX 5VA |
|
| Indication Form | | | 7segment LED DISPLAY the Upper: PV(green), the Lower: SV(red) |
|
| Input | | |
 | Sensor input : Thermocouple : K(CA), J, R, E, S, B, T, C(permission resistance of 100Ω and |
| below per a wire) |
| Thermoscope resistor(RTD) : DIN PT 100Ω, JIS PT 100Ω(permission resistance |
| of 5Ω and below per a wire) |
| Power : DC 1~5V, 0~10V Electric current : DC4~20mA |
 | A sampling cycle : 250㎳ |
 | Permission resistance of wire : Thermocouple : 100Ω and below RTD : 5Ω and below per a wire |
| Power : 1KΩ and below |
 | Permission input power : within ±10V |
 | Measure : FULL SCALE within ±0.3% |
 | Remote input : working by the value that is stored on SV of this gauge through the input of DC4~ |
| 20 outside |
|
|
| OUT1 | | |
 | A relay output ㆍ contact capacity : 250 VAC 5A 30 VDC 5A ㆍ contact constituent : 1C |
| ㆍ control system : P.I.D control(conversion of direction/ inverse) |
| ㆍ ON/OFF control(conversion of direction/ inverse) |
 | SSR output ㆍ ON power : about 24VDC and above(when there is disconnection and load |
| resistance 600and above, limits electric current of about 30mA) |
| ㆍOFF power : 0.1VDC and below ㆍA ratio cycle : 1~120/a second |
| ㆍControl system : time ratio P.I.D |
 | Electric current, Power output |
| ㆍcontrol of DC4~20mA electric current(conversion of direction/ inverse, slow start, with a built |
| in limit function of output upper and lower), transmission output (PV) |
| ㆍcontrol output of DC1~5V power, transmission output of power (using 250Ω resistance) |
|
|
| OUT2 | | |
 | A relay output ㆍContact capacity : 250 VAC 2A 30 VDC 2A ㆍContact constituent : 1A |
| ㆍControl system : ON/OFF control, SV different from Out1, setting up direction |
| / inverse |
| ㆍAlarm output : 6 kinds of alarm output and a heater disconnection alarm, |
| waiting for alarm |
| ㆍTimer output: 999minitues, seconds ON/OFF timer |
|
|
| OUT3 | | |
 | A relay output ㆍ Contact capacity : 250 VAC 2A 30 VDC 2A ㆍ Contact constituent : 1A |
| ㆍ Control system : ON/OFF control , SV different from Out1, setting up direction |
| /inverse |
| ㆍAlarm output : 6 kinds of alarm output and waiting for alarm |
| ㆍTimer output: 999minitues, seconds ON/OFF timer |
|
|
| OUT4 | | |
 | Electric current, Power output | | Option |
| ㆍcontrol of DC4~20mA electric current(conversion of direction and inverse, slow |
| start, with a built in limit function of output upper and lower), transmission output |
| (PV) |
| ㆍcontrol output of DC1~5V power, transmission output of power (using 250Ω |
| resistance) |
 | When the input is selected by remote, if Out4 is set in transmission output, sends |
| the input remote value as it is |
|
|
| Remote control Transmission | | |
 | RS485 transmission ㆍNo. of connection lines : 1~99 | | Option |
| ㆍTransmission distance : within 1.2km |
| ㆍTransmission wire : two wires |
| ㆍTransmission speed : selection among 2400, 4800, 9600BPS | | |
|
|
| Control of programmer room | | | Pattern 20segments program control |
|
| Control of Manual Electric current | | | Manual control by registered value of 20mA DC values |
|
| Inside noise | | | 1KV R image and S image 1 ㎲ |
|
| Relay durability | | | Mechanical : one million times Electrical : three hundred thousands times |
|
| Temperature | | | 0~50℃ |
|
| Humidity | | | 20~85% |
|
| Special feature | | |
 | Selection of basic form PS485 transmission |
 | Multi-input/output function |
 | 3patterns 30segment program control |
 | Electric current, slow start, limit of electric current upper and lower |
 | ON/OFF timer(Out2,3) |
|
|
| Weight | | | 450g |